With the floor heating on and dinner cooking, the limiter cuts power to the whole flat. Switch things on and off to see where the limit is.
The figures are from the building's electrical design, except the ones marked as estimates. The 3 kW for the living-room floor is the value set on its thermostat. Floor heating switches fully on and fully off, so the power cuts look random: they come when the floor starts heating while someone is cooking.
The building's electrical design from November 2020 (glavni projekt, sheet 11.1) added up everything in the flat and assumed that about a quarter of it would ever run at once.
The list behind that sum has no living-room floor heating. The only floor heating in the design is the bathroom, drawn at 0.35 kW (the installed bathroom floor is 450 W). The 3 kW living-room floor came later, and the connection stayed the same size.
Photos of the flat's panel, the building's electrical design and the living-room thermostat.





The owner asks HEP ODS to raise the connection (povećanje priključne snage), and HEP swaps the limiter. The limiter is sealed and nobody else may touch it.
How the cost is worked out: the added kW × 193.00 €/kW, which is HEP ODS's unit price for a low-voltage connection, plus 25% VAT. That gives 277.44 € for 25 A and 665.85 € for 32 A. These are estimates; the binding amount is in HEP's offer. "Winter evening" means both floors heating and the hob on all zones, 6.7 kW.
An electrician should confirm on site that the flat's wiring suits the new current. On paper it does: the design shows a 3×10 mm² feed, and the main switch and RCD are rated 40 A.
These reduce the power cuts. The flat still cannot heat and cook at the same time.